for more product details, please call us:0731-84930888
for more product details, please call us:0731-84930888
适用于校准交流采样装置、交直流变送器、三相交直流电测仪表、同周期表等设备
准确度: 0.02 级 / 0.05 级可选
交流采样检测:可进行虚负荷校验 ( 标准源 ),或实负荷校验 ( 钳形夹测电流 )
变送器检测:检测电量变送器的基本误差,兼具直流纹波及响应时间的测量功能
谐波功能:三相电量可加载 2 ~ 21 次,幅度 / 相位均可调的谐波,进行谐波影响量试验
overview
model td4500, a multi-function apparatus for calibrating electrical power apparatuses and electrical measuring apparatuses. composed of three-phase source, dc source, three-phase measurement, dc small signal measurement or other functions. the optional accuracy classes are 0.05 and 0.02.
applied to calibrate the ac sampling devices by real load or virtual load in electric power system, and calibrate the three-phase apparatuses, dc apparatuses, transmitters and synchrometers.
meet the requirements of q/gdw 1899-2013 verification regulation calibration specification of ac sampling electrical measuring equipment. (tunkia is involved in drafting)
applications
features
● ac sampling calibration: the virtual load calibration method is using by three-phase source, and the real load calibration method is using by measuring current with the clamp online.
● transmitters measurement: measure the basic error, dc ripple and the response time for the transmitters.
● harmonic output: the output can load 2nd to 21st standard harmonics with adjustable amplitude and phase to test harmonic influence on the checked meters.
● value adjustment method: fixed-point, rotary encoder, step and potentiometer (option).
● phasor diagram: freely adjust the phase between the three-phase electrical parameters, and intuitively display by phasor diagram.
● excellent human-computer interaction: large lcd touch screen display, touch and button operation modes, easy for users to measure manually.
● periodic meters calibration (option): the fourth voltage output can calibrate the difference of amplitude, phase and frequency for periodic meters.
● proprietary software (option): support the calibration for the checked meters by semi-automatic or full-automatic, data management and report export.
electrical specifications
three-phase voltage / current output
output characteristics
● output range of voltage: 6 v to 456 v
● output range of current: 0.1 a to 6 a
● resolution: 0.002 % of range
● display: 6 digits
● distortion: <0.2 %
● protection: short-circuit protection, open-circuit protection and overload protection.
frequency, phase, harmonic and symmetry output
three-phase power output
output characteristics
● output range of ac power: combination of ac voltage range and ac current range.
● range of power factor: -1.0000…0.0000…+1.0000
three-phase voltage / current measurement
measurement characteristics
● measuring range of voltage: 6 v to 456 v
● measuring range of current: 0.1 a to 6 a
● display: 6 digits
● frequency: the range is from 45 hz to 70 hz, and the accuracy is ±0.01 hz.
● phase: the range is from 0.000 ° to 359.999 °, and the accuracy is ±0.1 °.
three-phase power measurement
dc voltage / current output (option)
output characteristics
● output range of voltage: 10 mv to 330 v
● output range of current: 0.1 ma to 22 ma
● resolution: 0.002 % of range
● display: 6 digits
● ripple coefficient: <1 %
● protection: short-circuit protection, open-circuit protection and overload protection.
dc small signal measurement
the fourth voltage output (option for synchrometer calibration)
● output range of voltage: 100 v and 380 v
● output margin of voltage: 0 to 110 % of range
● resolution: 0.002 % of range
● accuracy in 1 year: ±0.05 % of range
● display: 6 digits
● frequency: the range is from 45.000 hz to 55.000 hz, and the resolution is 0.001 hz.
● phase: the range is from 0.00 ° to 359.99 °, the resolution is 0.01 °, the accuracy is ±0.1 °.
general specifications
● line power: 220 v ±22 v, 50 hz ±2 hz
● operating environment: 0 °c to +40 °c, 20 % to 80 % r·h, non-condensing
● storage environment: -20 °c to +70 °c, <80 % r·h, non-condensing
● dimensions (w × h × d): 435 mm × 195 mm × 415 mm
● weight: 17 kg
● communication: rs-232 interface
selection guide