for more product details, please call us:0731-84930888
for more product details, please call us:0731-84930888
适用于检定三相交直流电测仪表、多功能电测仪表、交直流变送器及其他电测校准装置
准确度: 0.02 级 / 0.05 级可选
三相电量输出:电压最大达 825 v,电流最大达 55 a ( a 相为 110 a )
直流电量输出:电压最大达 1100 v,电流最大达 55 a
overview
model td4100, an intelligent and highly integrated calibrator for three-phase apparatuses. it integrates a variety of measurement and calibration functions, and can be regards as a small mobile electronic s laboratory. the optional accuracy classes are 0.02 and 0.05.
applied to calibrate three-phase apparatuses, multimeters, transmitters and other electrical measurement devices.
this calibrator complies with the following standards:
● jjg 124-2005 verification regulation of amperemeters, voltmeters, wattmeters and ohmmeters
● jjf 1284-2011 calibration specification of calibrators for electrical meters
● dl/t 1112-2009 verification code of verification equipment for ac&dc meter
applications
features
● three-phase electrical parameters output: the voltage is up to 825 v, and the current is up to 55 a (phase a is 110 a).
● dc electrical parameters output: voltage is up to 1100 v, current is up to 55 a.
● ac power output: active power, reactive power, apparent power and power factor.
● value adjustment method: fixed-point, rotary encoder, step and potentiometer (option).
● phasor diagram: freely adjust the phase between the three-phase electrical parameters, and intuitively display by phasor diagram.
● excellent human-computer interaction: large lcd touch screen display, touch and button operation modes, easy for users to measure manually.
● harmonic (option): the ac output can load 2nd to 21st standard harmonics with adjustable amplitude and phase.
● transmitter measurement (option): measure the secondary signal of the transmitters.
● electric energy calibration (option): calibrate a single ac electric energy meter by the standard pulse i/o interface.
● proprietary software (option): support the calibration for the checked meters by semi-automatic or full-automatic, data management and report export.
● workbench (option): simple wiring and convenient operation. as shown below:
electrical specifications
three-phase voltage
output characteristics
● output range of voltage: 3 v to 825 v
● resolution: 0.002 % of range
● display: 6 digits
● distortion: <0.2 %
● protection: short-circuit protection, overload protection.
three-phase current
output characteristics
● output range of current: 5 ma to 55 a (option 110 a for phase a)
● resolution: 0.002 % of range
● display: 6 digits
● distortion: <0.2 %
● protection: open-circuit protection, overload protection.
frequency, phase, harmonic and symmetry
three-phase power
output characteristics
● output range of ac power: combination of ac voltage range and ac current range.
● range of power factor: -1.0000…0.0000…+1.0000
dc voltage
output characteristics
● output range of voltage: 5 mv to 660 v (or 1100 v)
● resolution: 0.002 % of range
● display: 6 digits
● ripple coefficient: <1 %
● protection: short-circuit protection, overload protection.
dc current
output characteristics
● output range of voltage: 1μa to 33 a (or 55 a)
● resolution: 0.002 % of range
● display: 6 digits
● ripple coefficient: <1 %
● protection: open-circuit protection, overload protection.
dc small signal measurement (option)
ac electric energy (option)
● accuracy of active electric energy:
±0.1 % of reading @ class 0.05; ±0.05 % of reading @ class 0.02;
● accuracy of reactive electric energy:
±0.2 % of reading @ class 0.05; ±0.1 % of reading @ class 0.02;
● output of standard electric energy pulse: full scale @ 60 khz
● input of standard electric energy pulse: frequency ≤1 khz, input level from 3 v to 12 v
● constant of electric energy meter: 1…1000000 imp./kwh or 1…1000000 imp./ws
general specifications
● line power: 220 v ±22 v, 50 hz ±2 hz
● operating environment: 0 °c to +40 °c, 20 % to 80 % r·h, non-condensing
● storage environment: -20 °c to +70 °c, <80 % r·h, non-condensing
● dimensions (w × h × d): 560 mm × 200 mm × 530 mm (portable)
● dimensions (w × h × d): 1600 mm × 1050 mm × 800 mm (workbench)
● weight: 35.5 kg (portable)
● communication: rs-232 interface
selection guide