专用于检测电子式互感器,不仅可对比差及交差进行测量,还可对稳定性等进行全面评价
内置精密标准源,不需要外附调压器、升流器
实时显示被测量电量波形、频率、幅度及相位等。
可进行多次谐波分析及对电子式互感器的各次谐波精度进行校验
overview
model td4800, an apparatus for calibrating electronic instrument transformers. this apparatus is composed of ac voltage and ac current standard source as well as a small signal measurement from 0 to 6.25 v.
applied to calibrate the electronic instrument transformers with analog output or data transmission which of meeting iec 61850, and measure ratio difference and angle difference to make a comprehensive evaluation for the electronic instrument transformers.
reference standard
● iec 61869-11:2017 instrument transformers. part 11: additional requirements for low power passive voltage transformers
● gb/t 20840.7-2007 instrument transformers. part 7: electronic voltage transformers
● gb/t 20840.8-2007 instrument transformers. part 8: electronic current transformers
● jjg 313-2010 instrument current transformers
● jjg 314-2010 instrument voltage transformers
● jjg 1021-2007 instrument transformers in power system
● dl/t 668-1999 instrument transformer testing equipment for measuring service
features
● there are built-in ac voltage and ac current standard sources with high precision, no need for external voltage regulators and current risers.
● display the waveform, frequency, amplitude and phase of the measured parameters in real time.
● count and analyze the average, maximum variation, extreme and square deviation of ratio difference and angle difference.
● multiple harmonic analysis and accuracy calibration of each order harmonic for the electronic instrument transformers.
● dual sc fiber ethernet interface and rj45 ethernet interface.
electrical specifications
ac voltage and current output
output characteristics
● output range of voltage: 6 v to 120 v, the load power is more than 12 va.
● output range of current: 0.1 a to 6 a, the load power is more than 20 va.
● resolution: 0.001 % of range
frequency, phase and harmonic
ac measurement
● range: 100 mv, 200 mv, 500 mv, 1 v, 2 v, 5 v.
● measuring range: 0.1 v to 6.25 v
● accuracy of ratio difference: ± (0.03 % of read + 0.02 % of range)
● accuracy of angle difference: ±2 ′
clock synchronization
● supported mode: code irig-b of fiber or rj45 ethernet interface, pps io mode of fiber or electrical level and clock output mode of abnormal timing.
● error measurement: synchronization or out of synchronization
● clock accuracy in 1 year: ±1 ppm
general specifications
● line power: 220 v ±22 v, 50 hz ±2 hz
● operating environment: 0 °c to +40 °c, 20 % to 85 % r·h, non-condensing
● storage environment: -20 °c to +70 °c, <85 % r·h, non-condensing
● communication: rs-232 interface