专用于检测变电站自动化系统,准确度为 0.02 级 / 0.05 级可选
交流采样检测:可进行虚负荷校验 ( 三相标准源 ),或实负荷校验 ( 钳形夹测电流 )
变送器检测:检测电量变送器的基本误差,兼具直流纹波及响应时间的测量功能
电力自动化检测:可实现子站仿真,如遥信风暴仿真、保护事件动作模拟、五防逻辑检测等
谐波功能:三相电量可加载 2 ~ 21 次,幅度 / 相位均可调的谐波
overview
model td4600, a multi-function apparatus for field testing the automatic system of substation regularly. composed of three-phase source, dc source, three-phase measurement, dc small signal measurement or other functions. the optional accuracy classes are 0.02 and 0.05.
applied to calibrate the ac sampling devices by real load or virtual load in electric power system, and calibrate three-phase apparatuses, dc apparatuses, transmitters and periodic meters. there are other functions as following: accuracy of time calibration, teleindication storm test, teleindication anti-shake test, resolution test for soe, breaker simulation, network performance test, synchrometer calibration, monitoring and recording for protocol.
features
● harmonic output: the output can load 2nd to 21st standard harmonics with adjustable amplitude and phase to test harmonic influence on the checked meters.
● value adjustment method: fixed-point, rotary encoder, step and potentiometer adjustment methods are supported. the three-phase electrical parameters can be adjusted uniformly or separately.
● synchrometer calibration (option): the fourth voltage output can calibrate the difference of amplitude, phase and frequency for periodic meters.
● proprietary software (option): support the calibration for the checked meters by semi-automatic or full-automatic, data management and report export.
electrical specifications
three-phase voltage / current output
output characteristics
● output range of voltage: 6 v to 456 v
● output range of current: 0.1 a to 6 a
● resolution: 0.002 % of range
● display: 6 digits
● distortion: <0.2 %
● protection: short-circuit protection, open-circuit protection and overload protection.
frequency, phase, harmonic and symmetry output
three-phase power output
output characteristics
● output range of ac power: combination of ac voltage range and ac current range.
● range of power factor: -1.0000…0.0000…+1.0000
three-phase voltage / current measurement
measurement characteristics
● measuring range of voltage: 6 v to 456 v
● measuring range of current: 0.1 a to 6 a
● display: 6 digits
● frequency: the range is from 45 hz to 70 hz, and the accuracy is ±0.01 hz.
● phase: the range is from 0.000 ° to 359.999 °, and the accuracy is ±0.1 °.
three-phase power measurement
dc voltage / current output
output characteristics
● output range of voltage: 10 mv to 330 v
● output range of current: 0.1 ma to 22 ma
● resolution: 0.002 % of range
● display: 6 digits
● ripple coefficient: <1 %
● protection: short-circuit protection, open-circuit protection and overload protection.
dc small signal measurement
other
● the binary input is no less than 5 pairs, and the electricity is isolated from each other with the isolation voltage of 500 v.
● error of actuation time for the binary input: ≤1 ms
● compatible with idle contacts and active contacts, and can automatically identify the input polarity of active contacts from dc 24 v to 250 v.
● the output range is from 0 to 400 v when the idle contact is output.
● the common ports are shared, and the binary output that can be independently set to open or close is no less than 64 pairs.
● time error out of synchronization for the binary output: ≤0.1 ms
● there is a gps signal receiving module to output pps and code irir-b via the interfaces.
the fourth voltage output (option)
● output range of voltage: 100 v and 380 v
● output margin of voltage: 0 to 110 % of range
● resolution: 0.002 % of range
● accuracy in 1 year: ±0.05 % of range
● display: 6 digits
● frequency: the range is from 45.000 hz to 55.000 hz, and the resolution is 0.001 hz.
● phase: the range is from 0.00 ° to 359.99 °, the resolution is 0.01 °, the accuracy is ±0.1 °.
general specifications
● line power: 220 v ±22 v, 50 hz ±2 hz
● operating environment: 0 °c to +40 °c, 20 % to 80 % r·h, non-condensing
● storage environment: -20 °c to +70 °c, <80 % r·h, non-condensing
● dimensions (w × h × d): 415 mm × 190 mm × 415 mm
● weight: 16.5 kg
● communication: rs-232 interface