td6300 tester for electronic instrument transformers -凯发k8国际

for more product details, please call us:0731-84930888

homeelectrical measurementtransformer testing

td6300 tester for electronic instrument transformers

专用于测量电子式互感器比差、角差


交流电压与电流测量的准确度均为 0.01 级,频率 45 hz ~ 65 hz

在 50 hz / 60 hz 条件下,比差准确度达 ± 0.02%,相位移准确度达 ± 0.005°

支持多种单位显示:度、度分秒、弧度


overview

model td6300, a high-precision apparatus to measure the ratio difference and phase displacement for electronic instrument transformers. it has the function of vector measurement to the following parameters: the secondary voltage (maximum 120 v) and current (maximum 6 a) of standard transformers, the secondary ac output voltage (maximum 12 v) and current (maximum 1.2 a) of the detected electronic instrument transformers.

features

● the electronic voltage transformers or electronic current transformers are all supported for detecting.

● measure ac voltage, current and frequency, as well as measure the phase/ratio of v-v, v-i and i-i.

● the accuracy class of ac voltage or current measurement is 0.01 with a frequency of 45 hz to 65 hz.

● at 50 hz / 60 hz, the ratio difference measurement accuracy is up to ±0.02 %, and the phase displacement measurement accuracy is up to ±0.005 °.

● support for displaying multiple units, such as degree, degree-second-second and radian.

● all the input channels can automatically or manually switch the ranges.

● good electrical insulation and protection between all the input channels and measurement loops.

electrical specifications

ac voltage (u1) and current (i1) measurement

21

measurement characteristics

● measuring range of u1: 1 v to 120 v

● measuring range of i1: 5 ma to 6 a

● measuring range of frequency: 45 hz to 65 hz

● display: 7 digits

● protection: over-current protection

ac voltage (u2) and current (i2) measurement

6300

measurement characteristics

● range switching: automatic or manual

● measuring range of u2: 1 mv to 12 v

● measuring range of i2: 0.1 ma to 1.2 a

● measuring range of frequency: 45 hz to 65 hz

● display: 7 digits

● protection: over-current protection

frequency and phase

24

ratio difference and phase displacement measurement

● accuracy of ratio difference: ±0.02 % (the input value ≥50 % of the range value, without the error caused by the standard transformers)

● accuracy of phase displacement: ±0.005 ° or 88 μrad (the input value ≥50 % of the range value, without the error caused by the standard transformers)

● frequency range: 45 hz to 65 hz

● notes: the unit of phase displacement can be degree or radian.

general specifications

● line power: 220 v ±22 v, 50 hz ±2 hz

● maximum power consumption: 80 va

● operating environment: 0 °c to +40 °c, r·h from 20 % to 85 %, non-condensing

● storage environment: -20 °c to +70 °c, r·h <95 %, non-condensing

● dimensions (w × h × d): 380 mm × 190 mm × 320 mm

● weight: 7 kg

● communication: rs-232 interface




powered by © 2011-2013 inc.
网站地图